SMK-2000A
GENERAL INFORMATION
Model Type SMART KING
Model Name SMK-2000A
AC INPUT
AC Input Capacity on Battery 2000VA
AC Input Voltage (+/-) 25% at line input
AC Input Frequency 50 or 60 Hz+/-5% (auto sensing)
AC OUTPUT
AC Output Voltage Pure sine wave at +/-5% of nominal, -10% of nominal after low battery warning
AC Output Frequency 50 or 60 Hz +/- 0.5%
AC Output Voltage Regulation AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal. AVR decrease output voltage 15% below input voltage if +9% to +25% of nominal
PROTECTION
Protection Spike 320 Joules, 2ms
Protection EMI/RFI 10dB at 0.15 MHz, 50 dB at 30 MHz
Protection Overload UPS automatic shutdown if overload exceeds 110% nominal at 20 sec and 125% at 5 sec
Protection Unit Fuse for 110V models (600VA~2500VA) and 220V models (under 1250VA), breaker for 110V model (3000VA) and 220V models (above 1500VA)
Protection Transfer Time 2/4 milliseconds (typical), including detection time
Protection Short Protection UPS output cut off immediately or input fuse( or breaker) protection
BATTERY
Battery Type Hot swappable, sealed, maintenance-free lead acid, with 3 - 6 year lifetime
Battery Typical 4 hours (to 90% of full capacity)
Battery Protection Automatic self-test & discharge protection, replace battery indicator
BACKUP TIME
Battery Backup Time Full Load 8 min
Battery Backup Time Half Load 17 min
PHYSICAL
Physical Weight kgs Tower 30
Physical Weight lbs Tower 66.0
Physical Dimension mm Tower 170x450x226
Physical Dimension inch Tower 6.7x17.7x8.9
INDICATOR
LCD Indicators Status Indicate line, bypass, inv, backup, fault, bat capacity, load capacity, I/P frequency, O/P voltage, O/P frequency, inside temperature, fault status, load
LED LED
ALARM
Alarm Battery Backup Slow beeping sound (about 0.25 Hz)
Alarm Battery Low Rapid beeping sound (about 1.00Hz)
Alarm Overload Continue beeping sound
INTERFACE
Interface Dry Contact Sends AC fail and battery low signals, and receives shutdown signal from computer
Interface RS-232 Detect battery low, Schedule UPS on/off, AC input/output power status display
Interface Option Novell, SNMP, Windows NT, Window 95/98/2000/ME/XP
ENVIRONMENT
Environment Ambient 3,500 meters max. elevation, 0-95% humidity non-condensing, 0-48 deg c
Environment Audible <40dBA (1 meter from surface)
Environment Storage Condition 15,000 meters max. elevation