Home page Home page
About UsProducts Services SalesNews Contact Us

EBK-350S
GENERAL INFORMATION
Model Type E-Book
Model Name EBK-350S
AC INPUT
AC Input Voltage 100V +20% / -15% at line input, 110V / 115V +/- 20% at line input
AC Input Frequency 50 or 60 Hz+/-10% (auto sensing)
OUTPUT
Output Capacity 350VA
Output By Pass Capacity 400VA
Output No Of Sockets 3 UPS Sockets and 1 Bypass Socket
Output Voltage On Battery Simulated sine wave at 100V ro 110V/115V or 200V/240V +/- 5%
Output Transfer Time 2/4 milliseconds, including detection time
PROTECTION
Protection Overload UPS automatic shutdown if overload exceeds 105% of nominal at 20 sec, 120% at 10 sec, and 130% at 3 sec
Protection Unit Fuse for overload & short circuit protection
Protection Short Protection UPS output cut off immediately
BATTERY
Battery Type Sealed, Maintenance-free lead acid, with 3 - 6 years typical lifetime
Battery Typical 4 hours
Battery Protection Automatic self-test & over discharge protection, short circuit protection by fuse
Battery LED Indicator Battery Check
PHYSICAL
Physical Weight kgs 5.8
Physical Weight lbs 12.5lb
Physical Dimension mm 250x200x50
Physical Dimension inch 9.8
INDICATOR
LED LED
ALARM
Alarm Battery Backup Slow beeping sound every 4 seconds
Alarm Battery Low Rapid beeping sound every second
Alarm Overload Continue beeping sound, Overload LED always On
Alarm Battery 105% load Continue beeping sound every 4 seconds
INTERFACE
Interface Dry Contact Sends battery low & power failure signals, and receives shutdown signal from computer
Interface RS-232 Detect battery low, Schedule UPS on/off, AC input/output power status display
ENVIRONMENT
Environment Ambient 3,500 meters max. elevation, 0-95% humidity non-condensing, 0-40 deg c
Environment Audible <40dBA (1 meter from surface)
ShowOrder 5
Copyright 2002 Powercom America Inc. 623 South State College Blvd., Fullerton, California 92831 USA
Powered by GUS Networks, Inc.
All rights reserved.