Home page Home page
About UsProducts Services SalesNews Contact Us

ULT-10K31
 
GENERAL INFORMATION
Model Type ULTIMATE LCD
Model Name ULT-10K31
Power Rating 10KVA
AC INPUT
AC Input Voltage 170V~276V or 294V~478V
AC Input Frequency 50 or 60 Hz+/-3 Hz
AC Input Phase 3-4W
AC Input Power factor >= 0.95
AC OUTPUT
AC Output Voltage 110V/220V (1 - 3W Selectable)
AC Output Frequency 50Hz/60Hz (Auto detection)
AC Output Frequency Stability (+/-0.5%)
AC Output Voltage Regulation (+/-2%)
AC Output Powerfactor 0.7 (lagging)
AC Output Hamonic distortion <3% of T.H.D. at linear load
AC Output Overload detection 105% for 10 seconds and 130% +/- 10% for 300ms
EFFICIENCY
Field49 > 85%
TRANSFER
Transfer Power failure Recovery 0 ms
Transfer Overload Disappear Auto transfer to UPS
Transfer UPS to By Pass or Vice Versa 0 ms
NOISE
Noise Level 1m Distance < 55dBA
PROTECTION
Protection Spike 450 Joules
BATTERY
Battery Type Sealed lead acid battery, free-maintenance
Battery Protection Cut off without draining any current when battery low
Battery DC Voltage 240V
BACKUP TIME
Battery Backup Time Full Load 11 minutes
Battery Backup Time Half Load 28 minutes
Battery Recharge Time About 8 hours to 90% after fully discharged
PHYSICAL
Physical Weight kgs Tower 250
Physical Weight lbs Tower 550 (battery *40)
Physical Weight lbs RM N/A
Physical Dimension mm Tower 340x640x990
Physical Dimension inch Tower 13.3x25.2x38.6
INDICATOR
LCD LCD
LCD Indicators Status Indicate line, bypass, inv, backup, fault, bat capacity, load capacity, I/P frequency, O/P voltage, O/P frequency, inside temperature, fault status
ALARM
Alarm Battery Discharge The first warning will beep every 4 seconds to indicate battery in use. The second warning will beep every 1 second to signal battery low condition
Alarm UPS Fault Continuous beeping sound
INTERFACE
Interface Dry Contact Sends AC fail and battery low signals, and receives shutdown signal from computer
Interface RS-232 Detect battery low, Schedule UPS on/off, AC input/output power status display
Interface Option Novell, SNMP, Windows NT, Window 95/98/2000/ME/XP
ENVIRONMENT
Environment Temperature 0 deg C ~ 40 deg C
Environment Humidity 0%~95% (Non condensing)